For SAMSON DD 373x-5 rev 2 non enhanced DD (Tokenizer 4)
--------------------------------------------------------------
Lookup table for the 30 logger parameters 'M0' ... 'M29'
in directory <Diagnosis - Status messages - Logger>
--------------------------------------------------------------
Visible text| FF device | Description of the logged message   |
 in DD/HMI  | com. data |                                     |
--------------------------------------------------------------
    -   -------    0  ------- No message logged
    
    1   -------    1  ------- Init. error: x > range
    2   -------    2  ------- Init. error: Delta x < range
    3   -------    3  ------- Init. error: Mech./Pneu. (Attachment)
    4   -------    4  ------- Init. error: Init. time exceeded
    5   -------    5  ------- Init. error: Init./int. solenoid valve
    6   -------    6  ------- Init. error: Travel time too short
    7   -------    7  ------- Init. error: Pin position/safety switch
    8   -------    8  ------- Init. error: No emergency mode
    9   -------    9  ------- Init. error: Safety switch defective
    
    10  -------   10  ------- Oper. error: Control loop
    11  -------   11  ------- Oper. error: Zero point
    12  -------   12  ------- Oper. error: Autocorrection
    13  -------   13  ------- Oper. error: Fatal error
    15  -------   15  ------- Oper. error: Total valve travel exceeded
    AA  ------- 2000  ------- Oper. error: Mode unequal AUTO
    
    17  -------   17  ------- HW error: x-signal
    18  -------   18  ------- HW error: i/p converter
    19  -------   19  ------- HW error: Hardware
    20  -------   20  ------- HW error: Data memory
    21  -------   21  ------- HW error: Control calculation
    22  -------   22  ------- HW error: Program load error
    23  -------   23  ------- HW error: Initialization switch defective
    
    24  -------   24  ------- Data error: Control parameter
    25  -------   25  ------- Data error: Poti parameter
    26  -------   26  ------- Data error: Adjustment parameter
    27  -------   27  ------- Data error: General parameter
    28  -------   28  ------- Data error: Internal device error 1
    29  -------   29  ------- Data error: HART Parameter
    30  -------   30  ------- Data error: Info parameter
    31  -------   31  ------- Data error: Options parameter
    32  -------   32  ------- Data error: Diagnosis parameter
    
    33  -------   33  ------- Kp: manipulation
    34  -------   34  ------- Tv: manipulation
    
    51  -------   51  ------- Initialization was aborted
    H3  ------- 2001  ------- Set to fail-safe via SET_FAIL_SAFE_POS (Set to fail-safe position)
    H4  ------- 2002  ------- Valve diagnostics EXPERTplus deactivated
    H5  ------- 2003  ------- Valve diagnostics EXPERTplus activated
    H6  ------- 2004  ------- Internal communication error
    
    52  -------10000  ------- Range: Mostly near closing pos.
    53  -------10001  ------- Range: Mostly near max. opening
    54  -------10002  ------- Range: Mostly closing pos.
    55  -------10003  ------- Range: Mostly max. opening
    
    56  -------10005  ------- Trend range: Shift. work. range closing pos.
    57  -------10006  ------- Trend range: Shift. work. range max. opening pos.
    
    58  -------10008  ------- Limit range: Down
    59  -------10009  ------- Limit range: Up
    60  -------10010  ------- Limit range: Modification impossible
    
    61  -------10012  ------- Trend end pos.: ZP-shift mon.e down; aver. > ref.
    62  -------10013  ------- Trend end pos.: ZP-shift mon. up; aver. > ref.
    63  -------10014  ------- Trend end pos.: ZP-shift alt.; aver. > ref.
    64  -------10015  ------- Trend end pos.: ZP-shift mon. down; aver. < ref.
    65  -------10016  ------- Trend end pos.: ZP-shift mon. up; aver. < ref.
    66  -------10017  ------- Trend end pos.: ZP-alternate; aver. < ref.
    
    67  -------10019  ------- Mech. conn. Pos./Valve: No opt. travel transm.TEST
    68  -------10020  ------- Mech. conn. Pos./Valve: Perhaps loose
    69  -------10021  ------- Mech. conn. Pos./Valve: Perhaps limit. range
    
    70  -------10023  ------- Spring: Perhaps spring stiffness reduced TEST
    71  -------10024  ------- Spring: Perhaps bias reduced TEST
    72  -------10025  ------- Spring: Perhaps bias increased TEST
    73  -------10026  ------- Spring: Working at full capacity
    74  -------10027  ------- Spring: Working at full capacity TEST
    
    75  -------10029  ------- Air supply: Perhaps modified TEST
    76  -------10030  ------- Air supply: Perhaps not enough TEST
    77  -------10031  ------- Air supply: Perhaps not enough
    78  -------10032  ------- Air supply: Working at full capacity
    79  -------10033  ------- Air supply: Working at full capacity TEST
    80  -------10034  ------- Air supply: Perhaps modified
    
    81  -------10035  ------- Leakage Pneumatics: Perhaps existing TEST
    82  -------10036  ------- Leakage Pneumatics: Perhaps too large TEST
    83  -------10037  ------- Leakage Pneumatics: Perhaps too large
    84  -------10038  ------- Leakage Pneumatics: Perhaps existing
    
    85  -------10039  ------- Friction: Much higher over whole range
    86  -------10040  ------- Friction: Much lower over whole range
    87  -------10041  ------- Friction: Much higher over section
    88  -------10042  ------- Friction: Much lower over section
    
    89  -------10044  ------- Inner leakage: Alarm limit 2 exceeded
    90  -------10045  ------- Inner leakage: Alarm limit 3 exceeded
    91  -------10046  ------- Inner leakage: Perhaps existing
    
    92  -------10047  ------- Ext. leakage: Perhaps soon expected
    93  -------10048  ------- Ext. leakage: Perhaps existing
    94  -------10049  ------- Ext. leakage: Existing
    
    95  -------10060  ------- Temperature below -40C/-40F
    96  -------10062  ------- Temperature above +80C/+176F
    
    97  -------10070  ------- Data logger started by travel
    98  -------10071  ------- Data logger started by int. solenoid valve/forced vent.
    99  -------10072  ------- Data logger started by setpoint
    G7  -------10073  ------- Data logger started by int. sol. valve/forced venting
    G6  -------10074  ------- Data logger started by actual value
    G5  -------10075  ------- Data logger started by setpoint deviation
    G4  -------10076  ------- Data logger started by drive signal
    G3  -------10077  ------- Data logger started by binary input
    G2  -------10078  ------- Data logger started by condensed state
    G1  -------10079  ------- Data logger started by binary input 1
    F9  -------10080  ------- Data logger started by binary input 2
    H1  -------10081  ------- Data logger started by discrete output 1
    H2  -------10082  ------- Data logger started by discrete output 2
    
    F8  -------11020  ------- Mech. conn. Pos./Valve: Perhaps loose TEST
    
    F7  -------11039  ------- Friction: Much higher over whole range TEST
    F6  -------11040  ------- Friction: Much lower over whole range TEST
    F5  -------11041  ------- Friction: Much higher over section TEST
    F4  -------11042  ------- Friction: Much lower over section TEST
    
    F3  -------11100  ------- Diagnosis reset performed
    F2  -------11110  ------- No reference recording after initialization
    F1  -------12000  ------- Reset long-term histogram X
    E9  -------12001  ------- Reset long-term histogram cycle counter
    E8  -------12002  ------- Reset elapsed hours meter
    E7  -------12003  ------- Reset temp. meter and high. values
    E6  -------12004  ------- Reset long-term view Y-steady online
    E5  -------12005  ------- Reset long-term view hysteresis online
    E4  -------12006  ------- Reset end pos. trend ref. value upper end pos.
    E3  -------12007  ------- Reset end pos. trend ref. value lower end pos.
    E2  -------12008  ------- Long-term sound sensor: reset meas. whole range
    E1  -------12009  ------- Reset long-term process values histogram
    D9  -------12010  ------- Reset long-term histogram deviation
    D8  -------12021  ------- Current too low: i/p converter switched-off safely
    D7  -------12050  ------- Switching state determined via binary input
    D6  -------12051  ------- Local operation write protection activated via binary input
    D5  -------12052  ------- Partial Stroke Test (PST) activated via binary input
    D4  -------12053  ------- Set to fail safe reference variable via binary input
    D3  -------12054  ------- Switch between AUTO / MAN via binary input
    D2  -------12055  ------- Data logger launched via binary input
    D1  -------12056  ------- Reset diagnosis via binary input
    C9  -------12057  ------- External solenoid valve determined via binary input
    C8  -------12058  ------- Leakage detection determined via binary input
    C7  -------12450  ------- Leakage: abort. test d8: int. sol. valve
    C6  -------12451  ------- Leakage: abort. test d8: test time exceeded
    C5  -------12452  ------- Leakage: abort. test d8: meas. point not reachable
    C4  -------12453  ------- Leakage: abort. test d8: man. aborted
    C3  -------12461  ------- Leakage: abort. test d8: level alt. too small
    C2  -------12462  ------- Leakage: abort. test d8: level alt. too late
    C1  -------12470  ------- Leakage: abort. test d9: int. sol. valve
    B9  -------12471  ------- Leakage: abort. test d9: test time exceeded
    B8  -------12472  ------- Leakage: abort. test d9: meas. point not reachable
    B7  -------12473  ------- Leakage: abort. test d9: man. aborted
    B6  -------12481  ------- Leakage: abort. test d9: level alt. too small
    B5  -------12482  ------- Leakage: abort. test d9: level alt. too late
    B4  -------12490  ------- Leakage: reset analysis test d8
    B3  -------12491  ------- Leakage: reset analysis test d9
    B2  -------12492  ------- Leakage: reset short term diagram
    B1  -------12493  ------- Leakage: reset long term diagram
    A9  -------12494  ------- Leakage: reset level monitoring
    A8  -------12498  ------- Leakage: Cannot start test d9 - no test d8 started
    A7  -------12499  ------- Leakage: Alarm limit d9-test set to factory settings
    A6  -------12500  ------- Internal solenoid valve/forced venting activated
    A5  -------12510  ------- Overflow of the operating hours counter

    A4  -------12520  ------- PST: Status 'No test available' activated
    A3  -------12521  ------- PST: Status 'x cancellation' activated
    A2  -------12522  ------- PST: Status 'delta y cancellation' activated
    A1  -------12523  ------- PST: Status 'Tolerance band exceeded' activated
    Z  ------- 12524  ------- PST: Status 'Max. test time exceeded' activated
    Y  ------- 12525  ------- PST: Status 'Test manually cancelled' activated
    X  ------- 12526  ------- PST: Status 'Measured data storage out of memory' activated
    W  ------- 12527  ------- PST: Status 'Aborted by int. solenoid valve/forced venting' activated
    V  ------- 12528  ------- PST: Status 'Supply pressure / friction' activated
    U  ------- 12529  ------- PST successful
    T  ------- 12530  ------- PST: Status 'Difference w - step start too high' activated
    S  ------- 12531  ------- PST: Status 'Test aborted-ref. var. was changed' activated
    R  ------- 12532  ------- PST: Status 'Current too low' activated
    G8 ------- 12533  ------- PST: Status 'Test aborted - Max. break away time exceeded' activated
    G9 ------- 12534  ------- PST: Status 'Test aborted - Max. period to step end exceeded' activated

    Q  ------- 12544  ------- FST: Status 'Max. test time exceeded' activated
    P  ------- 12545  ------- FST: Status 'Test manually cancelled' activated
    O  ------- 12546  ------- FST: Status 'Measured data storage out of memory' activated
    N  ------- 12547  ------- FST: Status 'Aborted by int. solenoid valve/forced venting' activated
    M  ------- 12548  ------- FST: Status 'Supply pressure/friction' activated
    L  ------- 12549  ------- FST successful
    K  ------- 12550  ------- FST: Status 'Difference w - step start too high' activated
    I  ------- 12551  ------- FST: Status 'Test aborted - ref. var. was changed' activated
    H  ------- 12552  ------- FST: Status 'Current too low' activated
    GA ------- 12553  ------- FST: Status 'Test aborted - Max. break away time exceeded' activated
    GB ------- 12554  ------- FST: Status 'Test aborted - Max. period to step end exceeded' activated

    G  ------- 12600  ------- O/C: break loose time rising
    F  ------- 12601  ------- O/C: break loose time falling
    E  ------- 12602  ------- O/C: transit time rising
    D  ------- 12603  ------- O/C: transit time falling
    C  ------- 12604  ------- O/C: travel end value not reachable
    B  ------- 12605  ------- O/C: travel end value rising
    A  ------- 12606  ------- O/C: travel end value falling